variable speed drive, Altivar Process ATV600, APM, single 480V, 1400hp
Manufacturer: Schneider Electric
Part Number: ATV6A0M10T4
Key Specifications
| Range of product | Altivar Process ATV600 |
| Mounting mode | Cabinet mount |
| IP degree of protection | IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 | IP00 for IP21 or IP54 cabinet integration)IEC 60529 |
| Supply frequency | 50…60 Hz – 5…5 % |
| Network number of phases | 3 phases |
| [Us] rated supply voltage | 480 V – 15…10 % |
| Speed drive output frequency | 0…500 Hz |
| Nominal switching frequency | 2.5 kHz |
| Switching frequency | 2.5…8 kHz with derating factor | 2…8 kHz adjustable |
| Motor power kW | 1000.0 kW at 480 V normal duty | 800.0 kW at 480 V heavy duty |
| Motor power hp | 1400.0 hp at 480 V normal duty | 1100.0 hp at 480 V heavy duty |
| Line current | 1692.0 A 480 V normal duty) | 1362.0 A 480 V heavy duty) |
| Apparent power | 1172 kVA at 480 V normal duty | 944 kVA at 480 V heavy duty |
| Continuous output current | 1770.0 A at 2.5 kHz normal duty | 1420.0 A at 2.5 kHz heavy duty |
| Maximum transient current | 1947 A 60 s normal duty) | 2130 A 60 s heavy duty) |
| Permissible temporary current boost | 1.1 x In 60 s normal duty) | 1.5 x In 60 s heavy duty) |
| Output voltage | <= power supply voltage |
| Frequency resolution | Display unit 0.1 Hz | Analog input 0.012/50 Hz |
| Minimum switching current | Relay output R1, R2, R3 5 mA 24 V DC |
| Maximum switching current | Relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC | Relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC | Relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC | Relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC |
| Power dissipation in W | Forced convection 26820 W 2.5 kHz normal duty) | Forced convection 20380 W 2.5 kHz heavy duty) |